Model Number: CFT-380

  The CFT-380 Distribution Automation Feeder Terminal Unit is equipped with high-precision current and voltage measurement modules, along with accurate control logic. It efficiently performs fault diagnosis and handling, and it can be integrated with distribution devices such as load switches and circuit breakers. This terminal is suitable for monitoring and protecting the initial segment, main trunk lines, and critical branch circuits of the power grid, enabling real-time monitoring of the distribution network to maintain the stable operation of the power system.


  Specification

Parameter Category

Parameter Specification

Operating Power Supply

AC 220V ± 20%

Nominal Voltage Input

Phase Voltage: AC 3.25V; Zero Sequence Voltage: AC 6.5V/3

Nominal Current Input

Phase Current: AC 1V; Zero Sequence Current: AC 0.2V

Frequency

50Hz

Remote Signal Power Supply

DC 24V

Operating Power Supply

DC 220V (Permanent Magnet Operating Mechanism)

Communication Power Supply

DC 24V

Total Power Consumption

≤ 20VA (excluding communication module and backup power)

AC Voltage

1.5 times rated voltage: Continuous operation

AC Current

2 times rated current: Continuous operation; 20 times rated current: Allowed for 1 second

Voltage Measurement Accuracy

Phase Voltage ≤ 0.5% (Class 0.5); Zero Sequence Voltage: ≤ 0.5% (Class 0.5)

Current Measurement Accuracy

Phase Measurement ≤ 0.5% (≤ 1.2In); Phase Protection Value ≤ 3% (≤ 10In); Zero Sequence Current: Class 0.5

Power Measurement Accuracy

Active and Reactive Power Accuracy ≤ 1% (Class 1)

Energy Collection Accuracy

Active Energy: Class 0.5; Reactive Energy: Class 2

DC Sampling Accuracy

Class 0.5

Frequency Measurement Accuracy

≤ ±0.02Hz

Contact Capacity

AC 250V/5A; DC 24V 16A; DC 80V/2A or DC 110V/0.5A for resistive load

Backup Power Supply Performance

Backup power options include batteries (lead-acid or lithium) or supercapacitors

Inherent Action Time for Short-Circuit Protection

≤ 20ms

Accuracy of Time Setting Value

≤ ±1% or 40ms

Timekeeping Accuracy (Daily Error)

≤ 1s

Protection Performance

IP65

Industrial Grade Product

Operating Temperature Range (-40°C to +70°C); Resistant to magnetism, vibration, moisture, lightning, dust, and corrosion

Mean Time Between Failures

≥ 50,000 hours

Remote Control Contact Lifespan

100000 Times