1.overview
The ZW20-12 Three-Phase Combined Box Type Pole-Mounted Circuit Breaker system utilizes vacuum arc extinguishing technology and SF6 gas for external insulation, providing stable and reliable interruption performance. The product features a fully enclosed structure with excellent sealing capabilities, strong moisture resistance, and anti-condensation properties, making it suitable for use in hot and humid areas. It is primarily used for interrupting and closing load currents, overload currents, and short-circuit currents in power systems. This equipment is suitable for protection and control in substation and industrial distribution systems, and it is particularly well-suited for rural power grids and locations with frequent operations.
2.Technical Specifications
Parameter Category |
Parameter Index |
||
Rated Voltage |
12 kV |
||
Rated Insulation Level |
1-minute Rated Power Frequency Withstand Voltage |
Wet test |
Phase-to-phase and phase-to-ground: 30 kV; Breaker contacts: 34 kV |
Dry test |
Phase-to-phase and phase-to-ground: 42 kV; Breaker contacts: 48 kV |
||
Rated Lightning Impulse Withstand Voltage (Peak Value) |
Phase-to-phase and phase-to-ground |
75 kV |
|
Breaker |
85 kV |
||
Rated Current |
630 A |
||
Rated Short-Circuit Breaking Current |
20 kA、25 kA |
||
Rated Short-Circuit Closing Current (Peak Value) |
50 kA、63 kA |
||
Rated Dynamic Stability Current (Peak Value) |
50 kA、63 kA |
||
Rated Thermal Stability Current (RMS Value) |
20 kA、25 kA |
||
Rated Short-Circuit Breaking Operations |
30times |
||
Rated Thermal Stability Duration |
4s |
||
Rated Operating Sequence |
O-0.3s-CO-180s-CO |
||
Mechanical Life |
10000times |
||
Permissible Contact Wear Thickness |
3 mm |
||
Weight |
177 kg |
3.operating environment
1. Ambient Temperature: Minimum Temperature: -50°C, Maximum Temperature: +70°C, Maximum Daily Temperature Difference: 25°C
2. Ambient Humidity: Daily Average Relative Humidity: ≤ 95% , Monthly Average Relative Humidity: ≤ 90%
3. Altitude: ≤ 2000 m (customization required for altitudes above 2000 m)
4. Pollution Level: Level IV
5.Operating Environment: Outdoor, areas without flammable or explosive hazards, chemical corrosion and frequent severe vibrations